Analysis of Natural and Artificial Lighting Assessment for SNI Compliance in Physics Laboratories

Authors

  • Danang Purwanto Universitas Negeri Yogyakarta
  • Fadhil Muhammad Universitas Negeri Yogyakarta
  • Akhmad Mujiburrokhman Universitas Negeri Yogyakarta

DOI:

https://doi.org/10.37253/leader.v3i4.11266

Keywords:

Illuminance, Lighting Uniformity, Color rendering index, SNI 03-7062-2004, Physics laboratory

Abstract

Lighting quality in educational laboratories plays a crucial role in supporting visual comfort, health, and accuracy during practical activities. According to the Indonesian National Standard (SNI 03-7062-2004), the minimum required illuminance for laboratories is 500 lux. This study aims to evaluate the lighting level in the Physics Laboratory at Universitas Negeri Yogyakarta by comparing natural lighting (lamps off) and combined natural–artificial lighting (lamps on). Measurements were conducted using a digital lux meter at a working plane of 0.80 m across 25 grid points. Data collection was carried out at three time intervals—morning (09.00–10.00), noon (12.00–13.00), and afternoon (15.00–16.00)—with three replications each. Results show that natural lighting alone cannot meet the standard, with maximum values of only 217.89 lux at noon and as low as 33.15 lux in the afternoon. In contrast, artificial lighting significantly increased illuminance, reaching 568 lux in the morning, 620.1 lux at noon, and 500.46 lux in the afternoon—all above the required minimum. It is concluded that artificial lighting is essential to maintain adequate and stable illuminance in the laboratory. Regular maintenance and energy-efficient lamp systems are recommended to ensure both compliance and sustainability.

Downloads

Download data is not yet available.

References

S. I. Putri And S. Sudarti, “Analisis Intensitas Cahaya Di Dalam Ruangan Dengan Menggunakan Aplikasi Smart Luxmeter Berbasis Android,” J. Mater. Dan Pembelajaran Fis., Vol. 12, No. 2, Pp. 51–55, 2022.

[2] M. Pamungkas, H. Hafiddudin, And Y. S. Rohmah, “Perancangan Dan Realisasi Alat Pengukur Intensitas Cahaya. Elkomika: Jurnal Teknik Energi Elektrik, Teknik Telekomunikasi, & Teknik Elektronika, 3 (2), 120.” 2015.

[3] L. Cahyantari And B. Supriyadi, “Analisis Intensitas Pencahayaan Di Ruang Kuliah Gedung Fisika Universitas Jember Dengan Menggunakan Calculux Indoor 5.0 B,” J. Pembelajaran Fis., Vol. 5, No. 1, Pp. 77–78, 2017.

[4] Z. Atmam And Z. Zulfahri, “Analisis Intensitas Penerangan Dan Penggunaan Energi Listrik Di Laboratorium Komputer Sekolah Dasar Negeri 150 Pekanbaru,” In Seminar Nasional Teknologi Informasi Komunikasi Dan Industri (Sntki), 2015, Vol. 7.

[5] L. M. Parera, H. K. Tupan, And V. Puturuhu, “Analisis Pengaruh Intensitas Penerangan Pada Laboratorium Dan Bengkel Jurusan Teknik Elektro,” J. Simetrik, Vol. 8, No. 1, 2018.

[6] B. Guntur And G. M. Putro, “Analisis Intensitas Cahaya Pada Area Produksi Terhadap Keselamatan Dan Kenyamanan Kerja Sesuai Dengan Standar Pencahayaan,” Opsi, Vol. 10, No. 2, Pp. 115–124, 2017.

[7] F. O. Hutauruk, A. Atmam, And U. Situmeang, “Analisis Intensitas Pencahayaan Pada Lapangan Planet Futsal Rumbai Pekanbaru,” Sainetin (Jurnal Sains, Energi, Teknol. Ind., Vol. 2, No. 1, Pp. 1–10, 2017.

[8] A. M. Mappalotteng And S. Syahrul, “Analisis Penerangan Pada Ruangan Di Gedung Program Pascasarjana Unm Makassar,” Indones. J. Fundam. Sci., Vol. 1, No. 1, 2015.

[9] T. B. Sitorus, F. H. Napitupulu, And H. Ambarita, “Korelasi Temperatur Udara Dan Intensitas Radiasi Matahari Terhadap Performansi Mesin Pendingin Siklus Adsorpsi Tenaga Matahari,” Cylind. J. Ilm. Tek. Mesin, Vol. 1, No. 1, Pp. 8–17, 2014.

[10] O. Ayan And B. Turkay, “Iot-Based Energy Efficiency In Smart Homes By Smart Lighting Solutions,” In 2020 21st International Symposium On Electrical Apparatus & Technologies (Siela), 2020, Pp. 1–5.

[11] H. U. A. Zaky, O. C. Dewi, And C. D. Sulistiani, “Daylight And Artificial Lighting Integration In Achieving Lighting Uniformity In Educational Building,” J. Archit. Res. Des. Stud., Vol. 7, No. 1, Pp. 40–49, 2023.

[12] M. Pamungkas, H. Hafiddudin, And Y. S. Rohmah, “Perancangan Dan Realisasi Alat Pengukur Intensitas Cahaya,” Elkomika J. Tek. Energi Elektr. Tek. Telekomun. Tek. Elektron., Vol. 3, No. 2, P. 120, 2015.

[13] I. E. S. L. Handbook, “Illuminating Engineering Society,” New York, Vol. 23, 1972.

[14] C. G. Irianto, “Studi Optimasi Sistem Pencahayaan Ruang Kuliah Dengan Memanfaatkan Cahaya Alam,” Jur. Tek. Elektro-Fti, Univ. Trisakti. Jakarta Jetri, Vol. 5, Pp. 1–20, 2006.

[15] A. F. E. Wiyanto, “Analisis Pencahayaan Alami Dan Buatan Pada Ruang Kantor Terhadap Kenyamanan Visual Pengguna,” J. Patra, Vol. 3, No. 1, Pp. 33–42, 2021.

[16] N. Heindri, O. C. Dewi, And A. D. Ismoyo, “Lighting System Evaluations Of Working Space In Educational Building, Universitas Indonesia,” In Iop Conference Series: Earth And Environmental Science, 2022, Vol. 998, No. 1, P. 12029.

[17] M. A. Hardiansyah, “Efektivitas Pencahayaan Terhadap Kenyamanan Visual Pengguna Dan Pengunjung Dealer Mobil. Studi Kasus: Honda Internusa Makassar.” Universitas Hasanuddin, 2021.

[18] Y. Hu, M. R. Luo, And Y. Yang, “A Study On Lighting Uniformity For Led Smart Lighting System,” In 2015 12th China International Forum On Solid State Lighting (Sslchina), 2015, Pp. 127–130.

[19] T. Tsesmelis, I. Hasan, M. Cristani, F. Galasso, And A. Del Bue, “Rgbd2lux: Dense Light Intensity Estimation With An Rgbd Sensor,” In 2019 Ieee Winter Conference On Applications Of Computer Vision (Wacv), 2019, Pp. 501–510.

[20] SNI 03-6575, Tata Cara Perancangan Sistem Pencahayaan Buatan Pada Bangunan Gedung. 2021.

[21] SNI 16-7062, Pengukuran Intensitas Penerangan Di Tempat Kerja. 2024.

Downloads

Published

2025-08-30

Issue

Section

Articles